  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 83
81
COMMAND
NAME
DESCRIPTION
NO.
COMMAND SYNTAX
COMMAND
ARGUMENT 1
ARGUMENT 2 ARGUMENT 3 ARGUMENT 4 RESPONSE
Optical
Outputs
Assigns action of the two
optical outputs. The optical
outputs can be assigned to:
D No Action (disabled*)
AL Low Flow Alarm
AH – High Flow Alarm
AR – Range between High &
Low Alarms
T1 Tot#1 Reading > limit
T2 Tot#2 Reading > limit
PO – Pulse Output
DE – Diagnostic Events
M Manual On (enabled)
9
O 1 (Output #1)
2 (Output #2)
D* O1:D or O2:D
AL
O1:AL or O2:AL
AH O1:AH or O2:AH
AR O1:AR or O2:AR
T1
O1:T1 or O2:T1
T2 O1:T2 or O2:T2
PO O1:PO or O2:PO
DE
O1:DE or O2:DE
M
O1:M or O2:M
S (read current
settings)
O1:D or O2:PO
Device
Function
Sets / Reads Device Function
Device Function:
M – Flow Meter
C – Flow Controller
10
DF
<Value>
M – Flow Meter
C – Flow
Controller
DF:<Value>
Example:
DF:M
DF:<Value>
Example:
DF:M
No Argument
(Returns Current
Device Function)